- Description
- Specifications
- Download
Application
Having obtained Group IIexplosion proof certification and (T) level temperature certification, CZ300 explosion proof control box is adapted for hazardous areas which consist of air mixed with explosive gas of group IIA, IIB, IIC, T1~T6, and explosive dust. It’s been widely used in explosion-prone places e.g. refining, oil extraction, gas production, chemical engineering, grain processing and storage, gas stations and so on.
Description
CZ300 explosion proof control box is atechnically mature Ex equipment. It can accommodate a certain size electrics accessory. Gaining strong protectionfrom its stainless steel closure, CZ300 products have been extensively applied in hazardous areas with explosive gases and dusts.
Features
l Stainless steel 304 / 316L
l Suit for indoor and outdoor mounting
l Easy to install and maintenance
l ATEX,IECEx double certification
l Ingress Protection: IP66, IP68(2m/2h), IP69
l Working Voltage: AC100V~AC240V50Hz/60HzorAC24V50Hz/60Hz or DC24VorDC48V
Overall Sizes & Installation Dimensions
Specification
Model |
Model | CZ300,CZ300-E,CZ300-N,CZ300-EN,CZ300-F, CZ300-EF,CZ300-NF,CZ300-ENF |
Name | Explosion Proof Box |
Certification |
Certificate Mark |
ATEX: ⅠM2Ex dbⅠ Mb
Ⅱ 2 G Ex db ⅡC T6 Gb Ⅱ 2D Ex tb ⅢC T80℃ Db IECEx: ExdbIICT6Gb /ExtbIIIT80℃ Db |
Certificate No. | ATEX: Presafe17ATEX 11327Xissue1 IECEx: IECExPRE18.0010Xissue1 |
Mechanical |
Material | Stainless steel 304, 316L (Optional) |
Ingress Protection | IP66,IP68(2m/2h), IP69 |
Cable Thread Hole | Four or sixM27×1.25 / M25×1.5 / M20×1.5 /M32×1.5 (Optional) |
Electricity |
Voltage | 100~240Va.c. 50/60Hzor24Va.c.50/60Hz or24Vd.c.or48Vd.c. |
Current | ≤1.5A |
Power Consumption | ≤40W(The total input power including the external loads connected to the power out module ) Excluding the power consumption of direct transfer terminals |
Lightning Protection (Optional) | TVS6000Vlightning protection, surge protection, conform toGB/T17626.54 |
Power Input | 100~240Va.c.50/60Hz |
Power Output | 100~240Va.c.50/60Hzor24Va.c. 50/60Hzor24Vd.c.or48Vd.c. |
Network Communication | 3 ways |
485Communication | 1 way |
Alarm Input (Optional) | 2 ways |
Alarm Output (Optional) | 2 ways (1way for washer) |
Audio Input (Optional) | 1 way |
Audio Output (Optional) | 1 way |
Washer Control(Optional) | DC24V or DC12VorSwitch quantity |
Analog Video (Optional) | 1 way |
Built-in Optical Fibre | Single Mode simplex fiber (standard) Multi mode duplex fiber (Optional) |
Single mode Maximum transmission distance of optical fiber | Single mode: 20kmStandard Configuration, 40km/60km/80km/100km(Optional); Multi mode: 500m (standard) |
connector | FC (standard) /SC/ST |
Environment |
Ambient Temperature | -40℃~+60℃ |
Air Pressure | 80KPa~110KPa |
Relative Humidity | 95% RH (+25℃) |
General |
Electrical connections | Integrated Cable |
External dimensions | Length 310mm×Width 275mm×Height 183mm |
Internal dimensions | ∅233×128 |
Weight | 14KG(without package) |
Installation | Wall mount by Base hole, Pole mount by pole bracket |